G4AD25 0 To 100 Volt Acdc Input |
![]() ![]() |
Nominal Input Range | 0 to 100 V true rms AC/DC | |
Input Over Range | 100 V to 263 V | |
Resolution |
24.4 mV from 0 to 100 V
48.8 mV from 100 to 200 V 97.7 mV from 200 to 263.7 V |
|
Input Response Time |
5% of scale change
63.2% of scale change 99.9% of scale change |
5 Volts/millisecond
63.2 Volts/200 milliseconds 99 Volts/1200 milliseconds |
DC Common Mode Rejection | -120 dB | |
AC Common Mode Rejection | -120 dB @ 60 Hz | |
Maximum Operating Common
Mode Voltage |
750 VDC or peak AC | |
Input vs Output
Zero Scale (1,920 Hz) Full Scale (9,600 Hz) |
0 V 100 V |
|
Accuracy | 0.5 V (0.5%) | |
DC Reversal | ± 0.3 V (0.3%) | |
Power Requirements |
24 VDC (± 0.5 V) @ 40 mA logic supply
5.5 V maximum @ 15 mA |
|
Input Resistance
Differential Common Mode |
1 mOhms 1,000 mOhms |
|
Ambient Temperature
Operating Storage |
0 to 70 ° C -25 to 85 ° C |
Rev: 04/13