OPT-G4OAC15

Product 76 of 131
Zoom
OPTO22 15VDC Logik Ausgabemodul Gen.4 Schaltmodul 12-140V/AC, 3A
plus VAT Weight: 0.2 kg RegulÀr Regular Neu New
G4OAC15 G4 AC Output 12-140 VAC, 15 VDC Logic
Opto 22 G4OAC15 Opto 22 Logo
Opto 22’s G4 AC output modules are used to control or switch AC loads. Each module provides up to 4000 volts of
optical isolation (transient) between field outputs and the control side of the circuit, and each features zero voltage turn-
on and zero current turn-off. This AC output module is equivalent to a single-pole, single-throw, normally open contact
(Form A, SPST-NO).

Typical applications for AC output modules include switching loads such as AC relays, solenoids, motor starters,
heaters, lamps, and indicators.

Units G4OAC15 G4OAC15A G4OAC24 G4OAC24A
Nominal line voltage VAC 120 120/240 120 120/240
Output voltage range VAC 12-140 24-280 12-140 24-280
Key feature
Current rating:
At 45 °C ambient
At 70 °C ambient

A
A

3
2

3
2

3
2

3
2
UL Motor Load Rating A 1.5 1.5 1.5 1.5
Isolation input-to-output
(transient):
1 ms
1 minute
volts

4000
1500


4000
1500


4000
1500


4000
1500
Off-state leakage at
nominal voltage (60 Hz)
mARMS 5 1.25/2.5 5 1.25/2.5
Logic voltage range VDC 10.5-16 10.5-16 19.5-32 19.5-32
Logic pickup voltage VDC 10.5 10.5 19.5 19.5
Logic dropout voltage VDC 1 1 1 1
Logic input current at
nominal logic voltage
mA 15 15 18 18
Control resistance
(Rc in schematic)
ohms 1 K 1 K 2.2 K 2.2 K
One-cycle surge A peak 80 80 80 80
Turn-on time @ 60 Hz micro-
seconds
≤8.3* ≤8.3* ≤8.3* ≤8.3*
Turn-off time @ 60 Hz micro-
seconds
≤8.3** ≤8.3** ≤8.3** ≤8.3**
Peak repetitive voltage VAC 500 500 500 500
Minimum load current mA 20 20 20 20
Output voltage drop
maximum peak
V 1.6 1.6 1.6 1.6
Operating frequency Hz 25-65 25-65 25-65 25-65
dV/dT-off-state V/micro-
second
200 200 200 200
dV/dT-commutating -- snubbed for 0.5
power factor load
snubbed for 0.5
power factor load
snubbed for 0.5
power factor load
snubbed for 0.5
power factor load
Temperature
Operating
Storage

°C
°C

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85
* One-half cycle maximum. Module turns on at the zero volt crossing of the AC sine wave.
** One-half cycle maximum. Module turns off at the zero current crossing of the AC sine wave.

Rev: 04/13

* plus shipping