AD6 0 To +5 VDC Input |
![]() ![]() |
|
AD6 |
AD6T |
AD7 |
AD9T |
Nominal Voltage Input |
0 to 5 VDC |
0 to 5 VDC |
0 to 10 VDC |
0 to 50 mVDC |
Over/Under
Range |
-.125 to 11 VDC |
-.125 to 11 VDC |
-.250 to 11 VDC |
-.125 to 110 mVDC |
Accuracy* |
± 5 mV |
± 5 mV |
± 10 mV |
± 100 mV |
Power Requirements |
16 mA at
+15 VDC |
35 mA at
+15 VDC |
16 mA at
+15 VDC |
35 mA at
+15 VDC |
*May be improved by the use of the "Set Offset" or "Set Gain" commands in the OPTOMUX command set. |
Input Response Time* |
5% of scale change in 8.5 ms 63% of scale change in 165 ms |
Resolution |
12-bits |
Isolation
|
|
Temperature
|
|
*AD6HS input response 100% step change in less than 3 milliseconds. |
Rev: 04/13