ICTD Temperature Probe For ICTD Analog Input Modules |
![]() ![]() |
Input Temperature Range |
- 40 °C to 100 °C |
Output |
233 µA
@ -40 °C |
Sensitivity |
1 µA/°K |
Input Response
Time |
5 %/7 °C/7.8
seconds |
Output Accuracy |
±0.5 °C @ 25 °C. Factory calibrated. |
Repeatability |
±0.25 °C |
Thermal Time Constant |
2.5 minutes typical (still air) |
Cable Length |
>2,000 ft (610 meters) |
Dimensions |
Overall
length: 39" (1 m) |
Rev: 04/13