OPT-OAC15A
OAC15A AC Output, 24-280 VAC, 15 VDC Logic |
![]() ![]() |
The OAC15A output module is used for controlling or switching AC loads of 12-140 VAC. Each module provides up to
4000 volts (transient) of optical isolation between the field devices and the control logic. This module is equivalent to a
single pole, single throw, normally open contact (FORM A, SPST-NO, Make). All AC output modules feature zero voltage
turn-on and zero current turn-off.
Typical uses and applications for AC output modules include switching the following loads:
Relays
Solenoids
Motor starters
Heaters
Lamps or indicators
One Cycle Surge |
80 amps peak |
Peak Repetitive Voltage |
500 Volts |
Operating Ambient Temperature |
-30 to 70 °C |
Isolation, Input-to-Output (Transient) |
4,000 Vrms |
Minimum Load Current |
20 milliamps |
Operating Frequency |
25–65 Hz |
Turn-on Time |
1/2 cycle maximum-zero voltage |
Turn-off Time |
1/2 cycle maximum-zero current |
DV/DT - Off-State |
200 volts/microseconds |
DV/DT - Commutating |
Snubbed for rated 0.5 power factor load |
Output Voltage Drop Maximum Peak |
1.6 volts |
Off-State Leakage |
|
Module Specifications
|
Units |
OAC5 |
OAC5A |
OAC5H |
OAC5A5 |
OAC15 |
OAC15A |
OAC24 |
OAC24A |
OAC24H |
Line Voltage - Nominal |
VAC |
120 |
240 |
240 |
120/240 |
120 |
240 |
120 |
240 |
240 |
Operating Voltage Range |
VAC |
12–140 |
24–280 |
24–280 |
24–280 |
12–140 |
24–280 |
12–140 |
24–280 |
24–280 |
Current Rating |
|
|
|
|
|
|
|
|
|
|
UL Motor Load Rating |
amps |
1.5 |
1.5 |
-- * |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
-- * |
Logic Voltage - Nominal |
VDC |
5 |
5 |
5 |
5 |
15 |
15 |
24 |
24 |
24 |
Logic Voltage Range (Vcc)** |
VDC |
2.5–8 |
2.5–8 |
2.5–8 |
2.5–8 |
9–16 |
9–16 |
18–32 |
18–32 |
18–32 |
Logic Pickup Voltage* |
VDC |
2.5 |
2.5 |
2.5 |
2.5 |
9 |
9 |
18 |
18 |
18 |
Logic Dropout Voltage |
VDC |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Logic Input Current-@ Normal Logic |
mA |
12 |
12 |
12 |
12 |
15 |
15 |
18 |
18 |
18 |
Control Resistance |
Ohms |
220 |
220 |
220 |
220 |
1K |
1K |
2.2K |
2.2K |
2.2K |
* Not UL approved |
|
Rev: 04/13