OPTO22 5VDC Logik Ausgabemodul Gen.1 Schaltmodul 24-280V/AC, 3A
plus VAT Weight: 0.2 kg RegulÀr Regular Neu New
OAC5A AC Output, 24-280 VAC, 5 VDC Logic
Opto 22 OAC5A Opto 22 Logo

The OAC5A output module is used for controlling or switching AC loads of 12-140 VAC. Each module provides up to
4000 volts (transient) of optical isolation between the field devices and the control logic. This module is equivalent to a
single pole, single throw, normally open contact (FORM A, SPST-NO, Make). All AC output modules feature zero voltage
turn-on and zero current turn-off.

Typical uses and applications for AC output modules include switching the following loads:

Relays
Solenoids
Motor starters
Heaters
Lamps or indicators
 

One Cycle Surge

80 amps peak

Peak Repetitive Voltage

500 Volts

Operating Ambient Temperature

-30 to 70 °C

Isolation, Input-to-Output (Transient)

4,000 Vrms

Minimum Load Current

20 milliamps

Operating Frequency

25–65 Hz

Turn-on Time

1/2 cycle maximum-zero voltage

Turn-off Time

1/2 cycle maximum-zero current

DV/DT - Off-State

200 volts/microseconds

DV/DT - Commutating

Snubbed for rated 0.5 power factor load

Output Voltage Drop Maximum Peak

1.6 volts

Off-State Leakage
@ Nominal Voltage - 60 Hz


5 milliamps rms
2.5 milliamps rms for OAC5A OAC15A,
and OAC24A @120 VAC

Module Specifications

 

Units

OAC5

OAC5A

OAC5H

OAC5A5
(NC)

OAC15

OAC15A

OAC24

OAC24A

OAC24H

Line Voltage - Nominal

VAC

120

240

240

120/240

120

240

120

240

240

Operating Voltage Range

VAC

12–140

24–280

24–280

24–280

12–140

24–280

12–140

24–280

24–280

Current Rating
  @ 45 °C Ambient
  @ 70 °C Ambient


amps
amps


3
2


3
2


4
2


3
2


3
2


3
2


3
2


3
2


4
2

UL Motor Load Rating

amps

1.5

1.5

-- *

1.5

1.5

1.5

1.5

1.5

-- *

Logic Voltage - Nominal

VDC

5

5

5

5

15

15

24

24

24

Logic Voltage Range (Vcc)**

VDC

2.5–8

2.5–8

2.5–8

2.5–8

9–16

9–16

18–32

18–32

18–32

Logic Pickup Voltage*

VDC

2.5

2.5

2.5

2.5

9

9

18

18

18

Logic Dropout Voltage

VDC

1

1

1

1

1

1

1

1

1

Logic Input Current-@ Normal Logic
Voltage (Iout in schematic diagram)

mA

12

12

12

12

15

15

18

18

18

Control Resistance
(Rc in schematic diagram)

Ohms

220

220

220

220

1K

1K

2.2K

2.2K

2.2K