© 2013 Uwe Wannags Hard-+ Software Distribution e.K (SWD)
OPT-SNAP-ODC-32-SNK
SNAP-ODC-32-SNK SNAP 32-channel Digital Output Module, 5-60 VDC Load Sinking |
![]() ![]() |
module. This module is ideal for OEMs and others with applications with high point counts, or for those requiring a large
number of digital output channels on one SNAP I/O rack. The high-density configuration reduces per-point costs of
digital I/O systems by providing up to eight times as many I/O channels in the same space.
Part of the SNAP PAC System, the module mounts on a SNAP PAC rack with a SNAP PAC brain or rack-mounted
controller. Analog, digital, and serial I/O modules can all be on the same rack. Such an I/O unit is also well suited for
PC-based control or for use as intelligent remote I/O for an Allen-Bradley MicroLogix or other RSLogix-based PLC
system, such as ControlLogix or CompactLogix.
For easy field wiring, use the SNAP-ODC-HDB breakout rack and the SNAP-HD-BF6 header cable. A wiring harness with
flying leads (SNAP-HD-CBF6) is also available.
NOTE: If you need a Factory Mutual-approved version, see the SNAP-ODC-32-SNK-FM.
SNAP-ODC-32-SRC
SNAP-ODC-32-SRC-FM |
SNAP-ODC-32-SNK
SNAP-ODC-32-SNK-FM |
|
Switching Voltage | 5–60 VDC | 5–60 VDC |
Nominal Switching
Voltage |
12–24 VDC | 12–24 VDC |
Logic Voltage and Current | 5 VDC ± 0.1 @ 150 mA | 5 VDC ± 0.1 @ 150 mA |
Maximum Off State
Voltage |
60 VDC | 60 VDC |
Output Leakage, Typical | <10 microamps per channel (60 V, 70 °C) | <10 microamps per channel (60 V, 70 °C) |
Maximum Load per Point | 0.25 A | 0.25 A |
Voltage Drop | 0.15 VDC @ 0.25 A | 0.15 VDC @ 0.25 A |
Surge (1 sec.) | 1 A | 1 A |
Output Arrangement |
32 output channels; 4 groups of 8 outputs
each. Points in each group share a common positive connection. |
32 output channels; 4 groups of 8 outputs
each. Points in each group share a common negative connection. |
Output Turn-On/Off Time | 100 microseconds | 100 microseconds |
Polling time from I/O
processor to module1 |
2–30 ms typical2 | 2–30 ms typical2 |
Indicators |
None; use optional OptoTerminal-G20
diagnostic display or breakout rack. |
None; use optional OptoTerminal-G20
diagnostic display or breakout rack. |
Maximum Number of HDD
Modules on One Mounting Rack |
16 | 16 |
Agency Approvals |
SNAP-ODC-32-SRC: UL, CE, RoHS, DFARS
SNAP-ODC-32-SRC-FM: CE, FM, RoHS, DFARS |
SNAP-ODC-32-SNK: UL, CE, RoHS, DFARS
SNAP-ODC-32-SNK-FM: CE, FM, RoHS, DFARS |
Torque, hold-down screws | 4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) |
Torque, connector screws | 5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) |
Warranty | Lifetime | Lifetime |
1 Affects turn-on and turn-off determination
2 Time varies based on the SNAP PAC I/O processor (brain or on-the-rack controller), processor configuration, and Ethernet host communication activity. |
Rev: 04/13