© 2013 Uwe Wannags Hard-+ Software Distribution e.K (SWD)
OPT-SNAP-TEX-FB16-H
SNAP-TEX-FB16-H 16-Point Breakout Board for SNAP I/O with Fuses and Bussed Power (120-240 V) |
![]() ![]() |
and a fuse-blown indicator for each of its 16 channels. In addition, it provides 120–240 volts of power to loads. Simply
attach the power source to a single spot in the middle of the rack, and power goes out to solenoids or switches,
depending on the module you’re using. The SNAP-TEX-FB16-H is used primarily for digital inputs and outputs.
CAUTION: Odd pins on the SNAP-TEX-FB16-H breakout board are connected. Use only straight-through (SNAP-TEX-CBS6)
or odd (SNAP-TEX-CBO6) cables with this board. See the data sheet for recommended module, cable, and
breakout board combinations.
Feature | SNAP-TEX-32 | SNAP-TEX-FB16-H | SNAP-TEX-FB16-L |
Use with I/O
modules |
2- or 4-channel analog
inputs/outputs; 4-channel digital inputs/outputs * |
4-channel digital inputs and
outputs 16- and 32-ch digital inputs/outputs |
4-channel digital inputs and
outputs 16- and 32-ch digital inputs/outputs |
Use with cables |
SNAP-TEX-CBE6 (even pins
connected), SNAP-TEX-CBO6 (odd pins connected), or SNAP-TEX-CBS6 (no connections), depending on module. |
4-ch modules:
SNAP-TEX-CBO6 (odd pins connected)** or SNAP-TEX-CBS6 (straight-through), depending on module. 16-ch modules: SNAP-HD-ACF6 32-ch modules: SNAP-HD-CBF6 |
4-ch modules:
SNAP-TEX-CBO6 (odd pins connected)** or SNAP-TEX-CBS6 (straight-through), depending on module. 16-ch modules: SNAP-HD-ACF6 32-ch modules: SNAP-HD-CBF6 |
Connectors |
32 spring connectors; accommo
dates eight 4-channel modules |
16 spring connectors; accommo
dates four 4-channel modules |
16 spring connectors; accommo
dates four 4-channel modules |
Fusing | none |
1 A, 250 V, fast-acting fuse for
each I/O point (16 total). Replace with Opto 22 PN SNAP-FUSE1AC (Wickman PN 19373-1A) |
1 A, 250 V, fast-acting fuse for
each I/O point (16 total). Replace with Opto 22 PN SNAP-FUSE1AC (Wickman PN 19373-1A) |
Indicators | none | 1 LED per fuse (16 LEDs total) | 1 LED per fuse (16 LEDs total) |
Bussed
power |
none | 120–240 V | 12–24 V |
Agency
Approvals |
CE, RoHS, DFARS | CE, RoHS, DFARS | CE, RoHS, DFARS |
Warranty | 30 months | 30 months | 30 months |
* Can also be used with 8-, 16-, or 32-channel digital and analog inputs (not thermocouples).
** IMPORTANT: Do NOT USE the FB16 breakout boards with a SNAP-TEX-CBE6 cable. The board has odd pins connected; the cable has even pins connected. |
Rev: 04/13