OPT-G4IAC24A

Product 852 of 1293
Zoom
OPTO22 24VDC Logik Eingabemodul Gen.4 Schaltmodul 180-280V/AC, Periode 40msec.
plus VAT Weight: 0.2 kg RegulÀr Regular Neu New
G4IAC24A G4 AC Input 190-280 VAC, 24 VDC Logic
Opto 22 G4IAC24A Opto 22 Logo
Opto 22’s G4 AC input modules are used to detect on/off AC voltage levels. Each module provides up to 4000 volts of
optical isolation (transient) between field inputs and the logic output of the circuit.

All AC input modules are designed with filtering on the input and a hysteresis amplifier, providing high noise rejection
and transient-free “clean” switching.

Typical applications for AC input modules include sensing the presence or absence of voltage, and sensing contact
closure from sources such as proximity switches, limit switches, float switches, selector switches, push buttons, toggle
switches, and thermostats.
Units G4IAC15 G4IAC15A G4IAC24 G4IAC24A
Input voltage range VAC or VDC 90–140 180–280 90–140 180–280
Key feature -- -- -- -- --
Input current at maximum line mA 5 5 5 5
Isolation, input-to-output (transient):
1 ms
1 minute

V
V

4000
1500

4000
1500

4000
1500

4000
1500
Turn-on time ms 20 20 20 20
Turn-off time ms 20 20 20 20
Input allowed for off-state mA, V 1.4, 40 0.7, 45 1.4, 40 0.7, 45
Nominal output supply voltage VDC 15 15 24 24
Output supply voltage range VDC 12-18 12-18 20-30 20-30
Output supply current at
nominal logic voltage
mA 15 15 15 15
Input resistance (R1 in schematic) ohms 28 K 70 K 28 K 70 K
Control resistance (Rc in schematic) ohms 1 K 1 K 2.2 K 2.2 K
Output voltage drop V @ 50 mA 0.4 0.4 0.4 0.4
Output current (sinking) mA 50 50 50 50
Peak repetitive voltage VAC 500 500 500 500
Output leakage with no input microamps @ 30 VDC 100 100 100 100
Transistor V breakdown 30 30 30 30
Temperature
Operating:
Storage:

°C
°C

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

Rev: 04/13

* plus shipping