© 2013 Uwe Wannags Hard-+ Software Distribution e.K (SWD)
OPT-G4IDC5-SWNC
G4IDC5-SWNC G4 DC Input - DC voltage, self-powered, normally closed |
![]() ![]() |
an external dry contact switch. The G4IDC5-SW senses switch closure. Each user-supplied switch is connected with two
wires. Because the module includes power for the switch, this module is particularly cost-effective when labor costs for
wiring external power are high.
Opto 22’s G4 DC input modules provide up to 4000 volts (transient) of optical isolation between field inputs and the logic
output of the circuit. This module is designed with filtering on the input and a hysteresis amplifier, providing high noise
rejection and transient-free, “clean†switching.
Typical applications for the G4IDC5-SW include sensing contact closure from sources such as proximity switches, limit
switches, selector switches, push buttons, photoelectric switches, and TTL-compatible devices.
Field Side Ratings | |
Open Circuit Voltage (Switch Open) | 11 VDC min., 13 VDC typical, 15 VDC max. |
Short Circuit Current (Switch Closed) | 6 milliamps nominal |
Minimum Off Resistance | ≥20 K ohms |
Maximum Allowable On Resistance
(Wire + Contact Resistance) |
500 ohms |
Logic Side Ratings | |
Logic Output Voltage for G4IDC5-SW
(normally open) |
<0.5 V max. (switch closed; LED on) @ 2 mA sinking
2.7 V min. (switch open; LED off) @ 0.4 mA sourcing |
Logic Output Voltage for G4IDC5-SWNC (normally closed) |
<0.5 V max. (switch open; LED on) @ 2 mA sinking
2.7 V min. (switch closed; LED off) @ 0.4 mA sourcing |
Maximum Operating Common Mode
Voltage (Field Term to Logic Connector) |
250 V |
Power Requirements: | 5 VDC (±0.25) @ 25 mA nom. |
Module Ratings | |
Number of Channels Per Module | 1 |
Turn-on Time | 8 msec typical |
Turn-off Time | 8 msec typical |
Input-to-output Isolation (transient) | 4000 V AC/DC |
Temperature |
0 °C to 70 °C, operating
-30 °C to 85 °C, storage |
Rev: 04/13