OPT-G4IDC5MA

Product 868 of 1293
Zoom
OPTO22 5VDC Logik Eingabemodul Gen.4 Schaltmodul 12-32V/DC, , with Manual/Auto Switch
plus VAT Weight: 0.2 kg RegulÀr Regular Neu New
G4IDC5MA G4 DC Input 10-32 VDC, 5 VDC Logic with Manual/Auto Switch
Opto 22 G4IDC5MA Opto 22 Logo
Opto 22’s G4 DC input modules are used to detect on/off DC voltage levels. Each module provides up to 4000 volts
(transient) of optical isolation between field inputs and the logic output of the circuit. Typical applications for DC input
modules include sensing the presence or absence of voltage and sensing contact closure from sources such as proximity
switches, limit switches, selector switches, push buttons, photoelectric switches, and TTL-compatible devices.

This module is designed with filtering on the input and a hysteresis amplifier, providing high noise rejection and
transient-free, “clean” switching.
Units G4IDC5K G4IDC5MA G4IDC15 G4IDC24
Input voltage range VDC
VAC
2.5–16
10–32
12–32
10–32
12–32
10–32
12–32
Key feature Highest speed Diagnostic switch
Input current at maximum line mA 30 25 25 25
Isolation, input-to-output (transient):
1 ms
1 minute

V
V

4000
1500

4000
1500

4000
1500

4000
1500
Turn-on time ms 0.025* 5 5 5
Turn-off time ms 0.025* 5 5 5
Input allowed for off-state mA, V 0.2, 1 1, 3 1, 3 1, 3
Nominal output supply voltage VDC 5 5 15 24
Output supply voltage range VDC 4.5–6 4.5–6 12-18 20-30
Output supply current at
nominal logic voltage
mA 12 12 15 18
Input resistance (R1 in schematic) ohms 500 1.5 K 1.5 K 1.5 K
Control resistance (Rc in schematic) ohms 220 220 1 K 2.2 K
Output voltage drop V @ 50 mA 0.4 0.4 0.4 0.4
Output current (sinking) mA 50 50 50 50
Output leakage with no input microamps @ 30 VDC 100 100 100 100
Transistor V breakdown 30 30 30 30
Temperature
Operating:
Storage:

°C
°C

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85
* At 5Vp-p square wave input, 50% duty cycle.

Rev: 04/13

* plus shipping