OPT-G4OAC5AMA
G4OAC5AMA G4 AC Output 24-280 VAC, 5 VDC Logic, with manual/auto switch |
![]() ![]() |
optical isolation (transient) between field outputs and the control side of the circuit, and each features zero voltage turn-
on and zero current turn-off. This AC output module is equivalent to a single-pole, single-throw, normally open contact
(Form A, SPST-NO).
Typical applications for AC output modules include switching loads such as AC relays, solenoids, motor starters,
heaters, lamps, and indicators.
The G4OAC5AMA features a manual-on/manual-off/automatic switch, ideal for diagnostic testing of control applications.
Units |
G4OAC5
G4OAC5FM* |
G4OAC5A
G4OAC5AFM |
G4OAC5A5
G4OAC5A5FM |
G4OAC5MA | G4OAC5AMA | |
Nominal line voltage | VAC | 120 | 120/240 | 120/240 | 120 | 120/240 |
Output voltage range | VAC | 12-140 | 24-280 | 24-280 | 12-140 | 24-280 |
Key feature | | | | Normally closed | Diagnostic
switch |
Diagnostic
Switch |
Current rating:
At 45 °C ambient At 70 °C ambient |
A A |
3 2 |
3 2 |
3 2 |
3 2 |
3 2 |
UL Motor Load Rating | A | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 |
Isolation input-to-output
(transient): 1 ms 1 minute |
volts | 4000 1500 |
4000 1500 |
4000 1500 |
4000 1500 |
4000 1500 |
Off-state leakage at
nominal voltage (60 Hz) |
mARMS | 5 | 1.25/2.5 | 1.25/2.5 | 5 | 1.25/2.5 |
Nominal logic voltage | VDC | 5 | 5 | 5 | 5 | 5 |
Logic voltage range | VDC | 4-8 | 4-8 | 4-8 | 4-8 | 4-8 |
Logic pickup voltage | VDC | 4 | 4 | 4 | 4 | 4 |
Logic dropout voltage | VDC | 1 | 1 | 1 | 1 | 1 |
Logic input current at
nominal logic voltage |
mA | 12 | 12 | 12 | 12 | 12 |
Control resistance
(Rc in schematic) |
ohms | 220 | 220 | 220 | 220 | 220 |
One-cycle surge | A peak | 80 | 80 | 80 | 80 | 80 |
Turn-on time @ 60 Hz | milliseconds | ≤8.3** | ≤8.3** | ≤8.3** | ≤8.3** | ≤8.3** |
Turn-off time @ 60 Hz | milliseconds | ≤8.3*** | ≤8.3*** | ≤8.3*** | ≤8.3*** | ≤8.3*** |
Peak repetitive voltage | VAC | 500 | 500 | 500 | 500 | 500 |
Minimum load current | mA | 20 | 20 | 20 | 20 | 20 |
Output voltage drop
maximum peak |
V | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 |
Operating frequency | Hz | 25-65 | 25-65 | 25-65 | 25-65 | 25-65 | dV/dT-off-state | V/micro-
second |
200 | 200 | 200 | 200 | 200 | dV/dT-commutating | -- | snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
Temperature
Operating: Storage: |
°C °C |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
* Part numbers ending in FM are Factory Mutual approved.
** One-half cycle maximum. Module turns on at the zero volt crossing of the AC sine wave. *** One-half cycle maximum. Module turns off at the zero current crossing of the AC sine wave. |