OPTO22 5VDC Logik Ausgabemodul Gen.4 Schaltmodul 5-60V/DC, 3A, Factory Mutual approved
plus VAT Weight: 0.2 kg RegulÀr Regular Neu New
G4ODC5FM G4 DC Output 5-60 VDC, 5 VDC Logic, Factory Mutual Approved
Opto 22 G4ODC5FM Opto 22 Logo
G4 DC output modules are used to control or switch DC loads. Each module provides up to 4000 volts of optical isolation
(transient) between field devices and control logic.

Typical applications for DC output modules include switching loads such as DC relays, solenoids, motor starters, lamps,
and indicators.
The G4ODC5FM is Factory Mutual approved. If you do not need FM approval, see the G4ODC5.

Units G4ODC5
G4ODC5FM*
G4ODC5A
G4ODC5AFM
G4ODC5MA G4ODC15 G4ODC24 G4ODC24A
Maximum line voltage VDC 60 200 60 60 60 200
Output voltage range VDC 5-60 5-200 5-60 5-60 5-60 5-200
Key feature Diagnostic switch
Current rating:
At 45 °C ambient
At 70 °C ambient

A
A

3
2

1
0.55

3
2

3
2

3
2

1
0.55
Isolation input-to-output
(transient):
1 ms
1 minute
volts

4000
1500


4000
1500


4000
1500


4000
1500


4000
1500


4000
1500
Off-state leakage at
nominal voltage (60 Hz)
mA 1 1 1 1 1 1
Control Resistance
(RC in schematic)
W 220 220 220 1 K 2.2 K 2.2 K
One-second surge A 5 5 5 5 5 5
Turn-on time micro-
seconds
100 100 100 100 100 100
Turn-off time micro-
seconds
750 750 750 750 750 750
Nominal logic voltage VDC 5 5 5 15 24 24
Logic voltage range VDC 4-8 4-8 4-8 10.5-16 19.5-32 19.5-32
Logic pickup voltage VDC 4 4 4 10.5 19.5 19.5
Logic dropout voltage VDC 1 1 1 1 1 1
Logic input current at
nominal logic voltage
mA 12 12 12 15 18 18
Temperature
Operating:
Storage:

°C
°C

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85
* Part numbers ending in FM are Factory Mutual approved.

Rev: 04/13