OPT-ODC24
ODC24 DC Output, 5-60 VDC, 24 VDC Logic |
![]() ![]() |
The ODC24 output module is used for controlling or switching DC loads of 5-60 VDC. Each module provides 4000 volts
(transient) of optical isolation between the field devices and the control logic.
Typical uses and applications for DC output modules include switching the following loads:
DC relays
DC solenoids
DC motor starters
DC lamps or indicators
PLC logic
One-second Surge |
5 A |
Operating Ambient Temperature |
-30 °C to 70 °C |
Isolation, Input-to-Output (Transient) |
4000 volts |
Turn-on Time |
100 µs |
Turn-off Time |
750 µs |
Output Voltage Drop Maximum Peak |
1.6 volts |
Module Specifications
|
UNITS |
ODC5 |
ODC5A |
ODC15 |
ODC15A |
ODC24 |
ODC24A |
Line voltage - max. |
VDC |
60 |
200 |
60 |
200 |
60 |
200 |
Operating voltage range |
VDC |
5–60 |
5–200 |
5–60 |
5–200 |
5–60 |
5–200 |
Current rating |
|
|
|
|
|
|
|
UL Motor Load rating |
Amps |
1.5 |
1 |
1.5 |
1 |
1.5 |
1 |
Off-state leakage @ max. voltage |
mA |
1 |
2 |
1 |
2 |
1 |
2 |
Logic voltage - nominal |
VDC |
5 |
5 |
15 |
15 |
24 |
24 |
Logic voltage range (Vcc) |
VDC |
2.5–8 |
2.5–8 |
9–16 |
9–16 |
18–32 |
18–32 |
Logic pickup voltage |
VDC |
2.5 |
2.5 |
9 |
9 |
18 |
18 |
Logic dropout voltage |
VDC |
1 |
1 |
1 |
1 |
1 |
1 |
Logic input current |
mA |
12 |
12 |
15 |
15 |
18 |
18 |
Control resistance |
Ohms |
220 |
220 |
1K |
1K |
2.2K |
2.2K |
Rev: 04/13