OPT-SNAP-ODC5R5

Product 1207 of 1293
Zoom
OPTO 22 SNAP 4-channel Dry Contact Digital Output Module, Normally Closed
plus VAT Weight: 0.2 kg RegulÀr Regular Neu New
SNAP-ODC5R5 SNAP 4-Ch Reed Relay Digital Output Module, Normally Closed
Opto 22 SNAP-ODC5R5 Opto 22 Logo
The SNAP-ODC5R5 is a digital output module that uses reed relays and does not provide optical isolation. Current rating
depends on the voltage the module is used with. This module is normally closed.
 
This module was designed for a low-voltage DC load that that is purely resistive (no inrush current). Because of its low
10 VA rating, this module cannot be used with inductive or capacitive loads (even very small loads) nor 120 VAC.
 
If you need Factory Mutual approved modules, see the SNAP-ODC5R5FM.
 
Part of the SNAP PAC System, the module mounts on a SNAP PAC rack with a SNAP PAC brain or rack-mounted
controller. Analog, digital, and serial I/O modules can all be on the same rack. Such an I/O unit is also well suited for
PC-based control or for use as intelligent remote I/O for an Allen-Bradley MicroLogix or other RSLogix-based PLC
system, such as ControlLogix or CompactLogix.
 
For easier, faster wiring, see SNAP TEX cables and breakout boards.
 
  SNAP-ODC5R SNAP-ODC5R5
Key Feature Dry contact
Normally open
Dry contact
Normally closed
Torque, hold-down screws 4 in-lb (0.45 N-m) 4 in-lb (0.45 N-m)
Torque, connector screws 5.26 in-lb (0.6 N-m) 5.26 in-lb (0.6 N-m)
Field Side Ratings (each channel)
Line Voltage - Range 0–100 VDC
0–130 VAC*
0–100 VDC
0–130 VAC*
Line Voltage - Nominal -- --
Current Rating 0.5 amps switching* 0.5 amps switching*
Surge Current 0.5 amps* 0.5 amps*
Minimum Load 0 mA 0 mA
Output Voltage Drop 0 volts 0 volts
Off-state Leakage 0 mA 0 mA
Peak Blocking Voltage 100 VDC / 130 VAC 100 VDC / 130 VAC
Fuse
(Common to all Channels)
Has four isolated channels.
User must provide own fusing.
Has four isolated channels.
User must provide own fusing.
Channel-to-channel
isolation
300 VAC
(1500 V transient)
300 VAC
(1500 V transient)
Logic Side Ratings
Pickup Voltage 4 V @ 5.5 mA 4 V @ 5.5 mA
Dropout Voltage 1 VDC 1 VDC
Control Resistance 220 ohms 220 ohms
Logic Supply Voltage 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC
Logic Supply Current 50 mA maximum 50 mA maximum
Module Ratings
Number of Channels Per
Module
4 4
Turn-on Time 500 usec 500 usec
Turn-off Time 500 usec 500 usec
Isolation
(Field Side to Logic Side)
1,500 volts (transient) 1,500 volts (transient)
Mechanical Life 200,000,000 cycles 200,000,000 cycles
Temperature 0 °C to 70 °C, operating
-30 °C to 85 °C, storage
0 °C to 70 °C, operating
-30 °C to 85 °C, storage
Agency Approvals CE, CSA, RoHS, DFARS CE, RoHS, DFARS
Warranty 30 months or mechanical life,
whichever comes first
30 months or mechanical life,
whichever comes first
* The current of the dry contact module must not exceed 10 VA power limit under steady state or momentary in-rush
conditions. For voltages at or below 20 volts, the current limit is 0.5 amps. For voltages above 20 volts, the maximum
allowable current is determined by the following equation:
Current Maximum = 10 VA / Voltage. Rating curve is in the data sheet.

Rev: 04/13

* plus shipping