COM-32103-3

Zoom
32103-3 Power Supply PS1040 (24V, 40W), DIN RAIL
Select
  • Mengenstaffelpreise:

  • Stück
  • 2.5 % Rabatt
  • 5 % Rabatt
  • 10 % Rabatt
  • 12.5 % Rabatt
  • 15 % Rabatt
  • 17.5 % Rabatt
  • 20 % Rabatt
zzgl. MwSt. Gewicht: 0.3 kg Empfohlen Empfohlen Neu Neu

32103-3 Power Supply PS1040 (24V, 40W), DIN RAIL

The 24V 40W DIN Rail Power Supply has universal AC input, air convection cooling, DIN rail install, a power indicator and short circuit protection. DIN rail power supplies are 100% full burn-in tested.

Part Number: 32103-3

  • Universal AC input
  • Short circuit, overload, over voltage protection
  • Air convection cooling
  • DIN rail installation
  • Built in DC OK active signal
  • NEC class 2/ LPS compliant
  • Power on LED indicator
  • No load power consumption < 0.75W
  • 24V 40W DIN Rail Power Supply is 100% full burn-in tested
 
 
System Specifications
Hardware
  • EnclosureUL Compliant fully isolated plastic
  • Installation MethodDIN RAIL (35MM)
  • DIN Rail SpecTS35/7.5 or TS35/15
  • LED IndicatorsOutput voltage status
  • Dimensions3.9" x 1.6" x 3.5" 
    9.91 x 4.06 x 8.89 cm
  • Product Weight0.55 lbs 
    249.48 g

Input Specifications

  • Connector TypeScrew Terminals
  • AC Voltage Range85-264VAC
  • Frequency Range47-63Hz
  • Efficiency (Typ.)88%
  • AC Current (Typ.)1.1A/115VAC
    0.7A/230VAC
  • Cold Start Inrush Current30A/115VAC
    60A/230VAC
  • Leakage Current< 1mA/240VAC
  • No Load Power Consumption< 0.75W

Output Specifications

  • Connector TypeScrew Terminals
  • DC Voltage24VDC
  • Rated Current1.7A
  • Current Range0-1.7A
  • Rated Power40.8W
  • Voltage Adjustable Range24 - 30VDC
  • Voltage Tolerance±1%
  • Ripple and Noise (Max)150mVp-p
  • Output Load Derating60% of full load at 70°C
  • Line Regulation±1%
  • Load Regulation±1%
  • Set-Up, Rise Time500ms, 30ms/230VAC
    500ms, 30ms/115VAC
  • Hold Up Time (Typ.)50ms/230VAC
    20ms/115VAC at full load
  • DC OK Active SignalRelay Contact Rating: 30/1A

Protection Specifications

  • Short Circuit/Overload
    • Overload Power105-150% of rated power
    • Overload Protection TypeConstant current limiting. Recovers automatically after fault condition is removed.
  • Over Voltage
    • Rated Voltage31.2-36VDC
    • Over Voltage Protection TypeShutdown output voltage, re-power on to recover
Environmental Specifications
  • Air temperature
    • System On-20 to 70° C
    • System Off-40 to 85° C
  • Vibration
    • Component10-500Hz, 2G 10 min./1 cycle, 60 min. each along X, Y, Z axes
    • MountingCompliance to IEC60068-2-6
  • Operating Humidity (non-condensing)20% to 90%
  • MTBF (Mean Time Between Failures)34.44 Years
Export Information
  • Packaged Shipping Weight0.65lbs 
    294.84 g
  • Package Dimensions4.5" x 2.0" x 4.1" 
    11.43 x 5.08 x 10.41 cm
  • UPC Code7-56727-32103-3
  • ECCN4A994
  • Schedule B Number8504.40.6007
Regulatory Approvals
  • EmissionsEuropean Standard EN61204-3
    European Standard EN55022
    Class B Limit
    IEC 1000-3-2/EN61000-3-2: Harmonic
    Class A Limit
    IEC 1000-3-2/EN61000-3-2: Flicker
  • ImmunityEuropean Standard EN61204-3
    European Standard EN55024:
    IEC 1000-4-2/EN61000-4-2: Electrostatic Discharge (ESD)
    IEC 1000-4-3/EN61000-4-3: Radiated Radio-Frequency (RF)
    IEC 1000-4-4/EN61000-4-4: Fast Transient/Burst
    IEC 1000-4-5/EN61000-4-5: Surge
    IEC 1000-4-6/EN61000-4-6: Conducted Disturbance
    IEC 1000-4-8/EN61000-4-8: Magnetic field
    IEC 1000-4-11/EN61000-4-11: Dips and Voltage Variations
  • SafetyUL 60950
  • Other Regulatory Approvals

Rev: 04/18