OPT-G4AD9
G4AD9 0 To +50 mV Input |
![]() ![]() |
The G4DA9 time proportional output (TPO) module provides digital control from a Mistic Analog brick or Modular
controller. The module is optically-isolated to 4,000 volts from field devices and features point-to-point electrical isolation.
The analog module mounts on any Opto 22 Brick or Modular controller, and is held in place with a captive screw. The
module switches 5-60 VAC, and together with a power SSR is ideal for controlling heater circuits.
G4AD6 | G4AD6HS | G4AD7 | G4AD7HS | G4AD9 | G4AD11 | G4AD12 | G4AD13 | G4AD22 | |
Nominal Voltage Input | 0 to 5 VDC | 0 to 5 VDC |
0 to 10 VDC |
0 to 10 VDC |
0 to 50 mV |
-5 to +5 VDC |
-10 to +10 VDC |
0 to 100 mV |
0 to 1 VDC |
Over/Under Range | -0.3 to
11 VDC |
-0.3 to
11 VDC |
-0.6 to
22 VDC |
-0.6 to 22 VDC |
-3.0 to 110 mV |
-5.6 to 21 VDC |
-11.2 to 42 VDC |
-6 to 220 mV |
-60 mV to 2.2 VDC |
Accuracy* | ± 5 mV | ± 5 mV | ± 10 mV | ± 10 mV | ± 100 µV | ± 10 mV | ± 20 mV | ± 100 µV | ± 1 mV |
Response Time % Of Scale Change 5% 63% |
8.4 msec 165 msec |
< 3 msec < 3 msec |
8.4 msec 165 msec |
< 3 msec < 3 msec |
2 msec 36 mse |
8.4 msec 165 msec |
8.4 msec 165 msec |
2 msec 36 msec |
< 3 msec < 10 msec |
* Accuracy figure requires use of gain and offset commands. |
Resolution | 12 bits |
Isolation (Transient)
Input-to-output Input-to-analog-supply |
4,000 Vrms 4,000 Vrms |
Ambient Temperature
Operating Storage |
-30 to 70°C -40 to 85°C |
Rev: 04/13