OPT-G4OAC5AFM
G4OAC5AFM G4 AC Output 24-280 VAC, 5 VDC Logic, Factory Mutual Approved |
![]() ![]() |
optical isolation (transient) between field outputs and the control side of the circuit, and each features zero voltage turn-
on and zero current turn-off. This AC output module is equivalent to a single-pole, single-throw, normally open contact
(Form A, SPST-NO).
Typical applications for AC output modules include switching loads such as AC relays, solenoids, motor starters,
heaters, lamps, and indicators.
This module is Factory Mutual approved. If you do not need FM approval, see the G4OAC5A.
Units |
G4OAC5
G4OAC5FM* |
G4OAC5A
G4OAC5AFM |
G4OAC5A5
G4OAC5A5FM |
G4OAC5MA | G4OAC5AMA | |
Nominal line voltage | VAC | 120 | 120/240 | 120/240 | 120 | 120/240 |
Output voltage range | VAC | 12-140 | 24-280 | 24-280 | 12-140 | 24-280 |
Key feature | | | | Normally closed | Diagnostic
switch |
Diagnostic
Switch |
Current rating:
At 45 °C ambient At 70 °C ambient |
A A |
3 2 |
3 2 |
3 2 |
3 2 |
3 2 |
UL Motor Load Rating | A | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 |
Isolation input-to-output
(transient): 1 ms 1 minute |
volts | 4000 1500 |
4000 1500 |
4000 1500 |
4000 1500 |
4000 1500 |
Off-state leakage at
nominal voltage (60 Hz) |
mARMS | 5 | 1.25/2.5 | 1.25/2.5 | 5 | 1.25/2.5 |
Nominal logic voltage | VDC | 5 | 5 | 5 | 5 | 5 |
Logic voltage range | VDC | 4-8 | 4-8 | 4-8 | 4-8 | 4-8 |
Logic pickup voltage | VDC | 4 | 4 | 4 | 4 | 4 |
Logic dropout voltage | VDC | 1 | 1 | 1 | 1 | 1 |
Logic input current at
nominal logic voltage |
mA | 12 | 12 | 12 | 12 | 12 |
Control resistance
(Rc in schematic) |
ohms | 220 | 220 | 220 | 220 | 220 |
One-cycle surge | A peak | 80 | 80 | 80 | 80 | 80 |
Turn-on time @ 60 Hz | milliseconds | ≤8.3** | ≤8.3** | ≤8.3** | ≤8.3** | ≤8.3** |
Turn-off time @ 60 Hz | milliseconds | ≤8.3*** | ≤8.3*** | ≤8.3*** | ≤8.3*** | ≤8.3*** |
Peak repetitive voltage | VAC | 500 | 500 | 500 | 500 | 500 |
Minimum load current | mA | 20 | 20 | 20 | 20 | 20 |
Output voltage drop
maximum peak |
V | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 |
Operating frequency | Hz | 25-65 | 25-65 | 25-65 | 25-65 | 25-65 | dV/dT-off-state | V/micro-
second |
200 | 200 | 200 | 200 | 200 | dV/dT-commutating | -- | snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
Temperature
Operating: Storage: |
°C °C |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
* Part numbers ending in FM are Factory Mutual approved.
** One-half cycle maximum. Module turns on at the zero volt crossing of the AC sine wave. *** One-half cycle maximum. Module turns off at the zero current crossing of the AC sine wave. |
Rev: 04/13