OPT-G4ODC5R5FM
G4ODC5MA G4 DC Output 5-60 VDC, 5 VDC Logic with Manual/Auto Switch |
![]() ![]() |
G4 DC output modules are used to control or switch DC loads. Each module provides up to 4000 volts of optical isolation
(transient) between field devices and control logic.
Typical applications for DC output modules include switching loads such as DC relays, solenoids, motor starters, lamps,
and indicators.
The G4ODC5MA features a manual-on/manual-off/automatic switch, ideal for diagnostic testing of control applications.
|
Units | G4ODC5 G4ODC5FM* |
G4ODC5A G4ODC5AFM |
G4ODC5MA | G4ODC15 | G4ODC24 | G4ODC24A |
Maximum line voltage | VDC | 60 | 200 | 60 | 60 | 60 | 200 |
Output voltage range | VDC | 5-60 | 5-200 | 5-60 | 5-60 | 5-60 | 5-200 |
Key feature | — | — | — | Diagnostic switch | — | — | — |
Current rating: At 45 °C ambient At 70 °C ambient |
A A |
3 2 |
1 0.55 |
3 2 |
3 2 |
3 2 |
1 0.55 |
Isolation input-to-output (transient): 1 ms 1 minute |
volts | 4000 1500 |
4000 1500 |
4000 1500 |
4000 1500 |
4000 1500 |
4000 1500 |
Off-state leakage at nominal voltage (60 Hz) |
mA | 1 | 1 | 1 | 1 | 1 | 1 |
Control Resistance (RC in schematic) |
W | 220 | 220 | 220 | 1 K | 2.2 K | 2.2 K |
One-second surge | A | 5 | 5 | 5 | 5 | 5 | 5 |
Turn-on time | micro- seconds |
100 | 100 | 100 | 100 | 100 | 100 |
Turn-off time | micro- seconds |
750 | 750 | 750 | 750 | 750 | 750 |
Nominal logic voltage | VDC | 5 | 5 | 5 | 15 | 24 | 24 |
Logic voltage range | VDC | 4-8 | 4-8 | 4-8 | 10.5-16 | 19.5-32 | 19.5-32 |
Logic pickup voltage | VDC | 4 | 4 | 4 | 10.5 | 19.5 | 19.5 |
Logic dropout voltage | VDC | 1 | 1 | 1 | 1 | 1 | 1 |
Logic input current at nominal logic voltage |
mA | 12 | 12 | 12 | 15 | 18 | 18 |
Temperature Operating: Storage: |
°C °C |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
* Part numbers ending in FM are Factory Mutual approved. |
Rev: 12/19