OPT-AD18T

Artikel 761 VON 1293
Zoom
OPTO 22 Typ T Thermocouple Input Module Isolated
zzgl. MwSt. Gewicht: 0.2 kg RegulÀr Regulär Neu Neu
AD18T T Thermocouple Input Isolated
Opto 22 AD18T Opto 22 Logo

 

AD17T

AD17T

AD18T

AD19T

Thermocouple
Type

R

S

T

E

Nominal Temperature
Range °C

0° to 960°

0° to 1034°

-200° to 224°

-100° to 435°

Nominal Temperature
Range °F

32° to 1760°

32° to 1893°

-328° to 435°

-148° to 815°

Over/Under Range
Capability °C

-50° to 1768°

-50° to 1768°

-200° to 400°

-100° to 900°

Over/Under Range
Capability °F

-58° to 3214°

-58° to 3214°

-328° to 752°

-148° to 1652°

Average Resolution

0.23 °C
  (200 to 960 °C)
0.35 °C
  (960 to 1768 °C)

0.25 °C
  (200 to 1034 °C)
0.48 °C
  (1034 to 1768 °C)

0.1 °C
  (-200 to 244 °C)
0.14 °C
  (244 to 400 °C)

0.13 °C
  (-100 to 435 °C)
0.23 °C
  (435 to 900 °C)

Accuracy*

± 5 °C
  (200 to 960 °C)
± 3.5 °C
  (960 to 1768 °C)

± 5.2 °C
  (200 to 1034 °C)
± 4.2 °C
  (1034 to 1768 °C)

± 3 °C
  (-100 to 224 °C)
± 2 °C
  (224 to 400 °C)

± 3 °C

Repeatability

± 2.5 °C
  (200 to 960 °C)
± 1.8 °C
  (960 to 1768 °C)

± 2.6 °C
  (200 to 1034 °C)
± 2.1 °C
  (1034 to 1768 °C)

± 1.0 °C
  (-100 to 0 °C)
± 0.6 °C
  (0 to 224 °C)
± 0.4 °C
  (224 to 400 °C)

± 0.8 °C
  (-100 to 0 °C)
± 0.6 °C
  (0 to 435 °C)
± 0.5 °C
  (435 to 900 °C)

Power Requirements

30 mA at +15 VDC
30 mA at -15 VDC

30 mA at +15 VDC
30 mA at -15 VDC

30 mA at +15 VDC
30 mA at -15 VDC

30 mA at +15 VDC
30 mA at -15 VDC

*Accuracy may be improved by the use of "Set Offset" and "Set Gain" commands in the OPTOMUX command set.

Rev: 04/13

* zzgl. Versandkosten