Sollten Sie trotz korrekter E-Mail-Adresse und bereits bestehender Registrierung weiterhin Probleme mit dem Login haben und auch keine "Passwort vergessen"-E-Mail erhalten, so wenden Sie sich bitte per E-Mail an: order@swd.de
AD18T T Thermocouple Input Isolated |
![]() ![]() |
|
AD17T |
AD17T |
AD18T |
AD19T |
Thermocouple
|
R |
S |
T |
E |
Nominal
Temperature |
0° to 960° |
0° to 1034° |
-200° to 224° |
-100° to 435° |
Nominal
Temperature |
32° to 1760° |
32° to 1893° |
-328° to 435° |
-148° to 815° |
Over/Under
Range |
-50° to 1768° |
-50° to 1768° |
-200° to 400° |
-100° to 900° |
Over/Under
Range |
-58° to 3214° |
-58° to 3214° |
-328° to 752° |
-148° to 1652° |
Average Resolution |
0.23 °C |
0.25 °C |
0.1 °C |
0.13 °C |
Accuracy* |
±
5 °C |
±
5.2 °C |
±
3 °C |
± 3 °C |
Repeatability |
±
2.5 °C |
±
2.6 °C |
±
1.0 °C |
±
0.8 °C |
Power Requirements |
30 mA at
+15 VDC |
30 mA at
+15 VDC |
30 mA at
+15 VDC |
30 mA at
+15 VDC |
*Accuracy may be improved by the use of "Set Offset" and "Set Gain" commands in the OPTOMUX command set. |
Rev: 04/13