OPT-G4IDC5

Artikel 859 VON 1293
Zoom
OPTO22 5VDC Logik Eingabemodul Gen.4 Schaltmodul 12-32V/DC, Periode 10msec.
zzgl. MwSt. Gewicht: 0.04 kg RegulÀr Regulär Neu Neu
G4IDC5 G4 DC Input 10-32 VDC, 5 VDC Logic
Opto 22 G4IDC5 Opto 22 Logo

Opto 22’s G4 DC input modules are used to detect on/off DC voltage levels. Each module provides up to 4000 volts
(transient) of optical isolation between field inputs and the logic output of the circuit. Typical applications for DC input
modules include sensing the presence or absence of voltage and sensing contact closure from sources such as proximity
switches, limit switches, selector switches, push buttons, photoelectric switches, and TTL-compatible devices.

This module is designed with filtering on the input and a hysteresis amplifier, providing high noise rejection and
transient-free, “clean†switching.

  Units G4IDC5 G4IDC5B G4IDC5D G4IDC5G
Input voltage range VDC
VAC
10-32
12-32
4–16
4–16
2.5–28
35–60
35–60
Key feature   Higher speed Higher speed
Input current at maximum line mA 25 45 30 6
Isolation, input-to-output (transient):
1 ms
1 minute

V
V

4000
1500

4000
1500

4000
1500

4000
1500
Turn-on time ms 5 0.05 1 10
Turn-off time ms 5 0.1 1.5 10
Input allowed for off-state mA, V 1, 3 0.7, 1 0.2, 1 0.7, 7
Nominal output supply voltage VDC 5 5 5 5
Output supply voltage range VDC 4.5–6 4.5–6 4.5–6 4.5–6
Output supply current at
nominal logic voltage
mA 12 12 12 12
Input resistance (R1 in schematic) ohms 1.5 K 300 900 10 K
Control resistance (Rc in schematic) ohms 220 220 470 220
Output voltage drop V @ 50 mA 0.4 0.4 0.4 0.4
Output current (sinking) mA 50 50 50 50
Output leakage with no input microamps @ 30 VDC 100 100 100 100
Transistor V breakdown 30 30 30 30
Temperature
Operating:
Storage:

°C
°C

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

-30 to +70
-30 to +85

 

Rev: 12/21