OPT-G4OAC15
G4OAC15 G4 AC Output 12-140 VAC, 15 VDC Logic |
![]() ![]() |
optical isolation (transient) between field outputs and the control side of the circuit, and each features zero voltage turn-
on and zero current turn-off. This AC output module is equivalent to a single-pole, single-throw, normally open contact
(Form A, SPST-NO).
Typical applications for AC output modules include switching loads such as AC relays, solenoids, motor starters,
heaters, lamps, and indicators.
Units | G4OAC15 | G4OAC15A | G4OAC24 | G4OAC24A | |
Nominal line voltage | VAC | 120 | 120/240 | 120 | 120/240 |
Output voltage range | VAC | 12-140 | 24-280 | 12-140 | 24-280 |
Key feature | | | | | |
Current rating:
At 45 °C ambient At 70 °C ambient |
A A |
3 2 |
3 2 |
3 2 |
3 2 |
UL Motor Load Rating | A | 1.5 | 1.5 | 1.5 | 1.5 |
Isolation input-to-output
(transient): 1 ms 1 minute |
volts | 4000 1500 |
4000 1500 |
4000 1500 |
4000 1500 |
Off-state leakage at
nominal voltage (60 Hz) |
mARMS | 5 | 1.25/2.5 | 5 | 1.25/2.5 |
Logic voltage range | VDC | 10.5-16 | 10.5-16 | 19.5-32 | 19.5-32 |
Logic pickup voltage | VDC | 10.5 | 10.5 | 19.5 | 19.5 |
Logic dropout voltage | VDC | 1 | 1 | 1 | 1 |
Logic input current at
nominal logic voltage |
mA | 15 | 15 | 18 | 18 |
Control resistance
(Rc in schematic) |
ohms | 1 K | 1 K | 2.2 K | 2.2 K |
One-cycle surge | A peak | 80 | 80 | 80 | 80 |
Turn-on time @ 60 Hz | micro-
seconds |
≤8.3* | ≤8.3* | ≤8.3* | ≤8.3* |
Turn-off time @ 60 Hz | micro-
seconds |
≤8.3** | ≤8.3** | ≤8.3** | ≤8.3** |
Peak repetitive voltage | VAC | 500 | 500 | 500 | 500 |
Minimum load current | mA | 20 | 20 | 20 | 20 |
Output voltage drop
maximum peak |
V | 1.6 | 1.6 | 1.6 | 1.6 |
Operating frequency | Hz | 25-65 | 25-65 | 25-65 | 25-65 | dV/dT-off-state | V/micro-
second |
200 | 200 | 200 | 200 | dV/dT-commutating | -- | snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
snubbed for 0.5
power factor load |
Temperature
Operating Storage |
°C °C |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
-30 to +70 -30 to +85 |
* One-half cycle maximum. Module turns on at the zero volt crossing of the AC sine wave.
** One-half cycle maximum. Module turns off at the zero current crossing of the AC sine wave. |
Rev: 04/13