OPT-SNAP-ODC5MA
SNAP-ODC5MA SNAP 4-Ch Isolated 5-60 VDC Digital Output Module with Manual/Auto Switches |
![]() ![]() |
The SNAP-ODC5MA provides four isolated channels of 5-60 VDC digital output, each switching a separate DC load. The
module features manual-on/manual-off/automatic switches that override output from the application and are ideal for
testing field device wiring.
Part of the SNAP PAC System, the module mounts on a SNAP PAC rack with a SNAP PAC brain or rack-mounted
controller. Analog, digital, and serial I/O modules can all be on the same rack. Such an I/O unit is also well suited for
PC-based control or for use as intelligent remote I/O for an Allen-Bradley MicroLogix or other RSLogix-based PLC
system, such as ControlLogix or CompactLogix.
For easier, faster wiring, see SNAP TEX cables and breakout boards.
SNAP-ODC5MA | SNAP-ODC5-i | SNAP-ODC5A-i | SNAP-ODC5ASNK | |
Key Feature |
Diagnostic switches Four isolated channels |
Four isolated channels | Four isolated channels | Load sinking |
Torque, hold-down screws |
4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) |
Torque, connector screws |
5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) |
Field Side Ratings (each channel) | ||||
Line Voltage - Range |
5–60 VDC | 5–60 VDC | 5–200 VDC | 5–200 VDC |
Line Voltage - Nominal |
5–48 VDC | 5–48 VDC | 5–200 VDC | 5–200 VDC |
Current Rating 0 °C to 70 °C Ambient |
2 amps per module 0.5 amps per channel |
3 amps per module | 3 amps per module | 3 amps per module |
Surge Current |
1.5 amps peak for 1 second |
5 amps peak for 1 second |
5 amps peak for 1 second |
5 amps peak for 1 second |
Minimum Load | 20 mA | 20 mA | 20 mA | 20 mA |
Output Voltage Drop |
1.6 volts max.@ 0.75 amps |
1.6 volts max.@ 0.75 amps |
1.6 volts max.@ 0.75 amps |
1.6 volts max.@ 0.75 amps |
Off-state Leakage | 1 mA @ 60 VDC | 1 mA @ 60 VDC | 1 mA @ 200 VDC | 1 mA @ 200 VDC |
Peak Blocking Voltage |
60 VDC | 60 VDC | 200 VDC | 200 VDC |
Fuse (Common to all Channels) |
Has four isolated channels. User must provide own fusing. |
Has four isolated channels. User must provide own fusing. |
Has four isolated channels. User must provide own fusing. |
250 VAC - 4A 5x20 mm Fast-acting Bell Fuse Part: BEL 5HF4 Opto 22 Part: SNAP-FUSE4AB |
Channel-to-channel isolation |
300 VAC (1500 V transient) |
300 VAC (1500 V transient) |
300 VAC (1500 V transient) |
Not applicable |
Logic Side Ratings | ||||
Pickup Voltage | 4 V @ 5.5 mA | 4 V @ 5.5 mA | 4 V @ 5.5 mA | 4 V @ 5.5 mA |
Dropout Voltage | 1 VDC | 1 VDC | 1 VDC | 1 VDC |
Control Resistance | 220 ohms | 220 ohms | 220 ohms | 220 ohms |
Logic Supply Voltage | 5 VDC ± 0.25 VDC | 5 VDC ± 0.25 VDC | 5 VDC ± 0.25 VDC | 5 VDC ± 0.25 VDC |
Logic Supply Current | 50 mA maximum | 50 mA maximum | 50 mA maximum | 50 mA maximum |
Module Ratings | ||||
Number of Channels Per Module |
4 | 4 | 4 | 4 |
Turn-on Time | 100 usec | 100 usec | 100 usec | 100 usec |
Turn-off Time | 750 usec | 750 usec | 750 usec | 750 usec |
Isolation, (Field Side to Logic Side) |
4,000 volts (transient) | 4,000 volts (transient) | 4,000 volts (transient) | 4,000 volts (transient) |
Temperature |
0 °C to 70 °C, operating -30 °C to 85 °C, storage |
0 °C to 70 °C, operating -30 °C to 85 °C, storage |
0 °C to 70 °C, operating -30 °C to 85 °C, storage |
0 °C to 70 °C, operating -30 °C to 85 °C, storage |
Agency Approvals | UL, CE, RoHS, DFARS | UL, CE, RoHS, DFARS | UL, CE, RoHS, DFARS | UL, CE, RoHS, DFARS |
Warranty | 30 months | Lifetime | Lifetime | Lifetime |
Rev: 04/13