OPT-SNAP-ODC5R5FM
SNAP-ODC5R5FM SNAP 4-Ch Reed Relay Digital Output Module, Normally Closed, Factory Mutual Approved |
![]() ![]() |
rating depends on the voltage the module is used with. This module is normally closed. It includes a connector clamp to
prevent sparks and is Factory Mutual (FM) approved.
This module was designed for a low-voltage DC load that that is purely resistive (no inrush current). Because of its low
10 VA rating, this module cannot be used with inductive or capacitive loads (even very small loads) nor 120 VAC.
Part of the SNAP PAC System, the module mounts on a SNAP PAC rack with a SNAP PAC brain or rack-mounted
controller. Analog, digital, and serial I/O modules can all be on the same rack. Such an I/O unit is also well suited for
PC-based control or for use as intelligent remote I/O for an Allen-Bradley MicroLogix or other RSLogix-based PLC
system, such as ControlLogix or CompactLogix.
If you do not need FM approval, see the SNAP-ODC5R5.
For easier, faster wiring, see SNAP TEX cables and breakout boards.
SNAP-ODC5RFM | SNAP-ODC5R5FM | |
Key Feature | Factory Mutual approved | Factory Mutual approved |
Torque, hold-down screws | 4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) |
Torque, connector screws | 5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) |
Field Side Ratings (each channel) | ||
Line Voltage - Range |
0–100 VDC
0–130 VAC* |
0–100 VDC
0–130 VAC* |
Line Voltage - Nominal | -- | -- |
Current Rating | 0.5 amps switching* | 0.5 amps switching* |
Surge Current | 0.5 amps* | 0.5 amps* |
Minimum Load | 0 mA | 0 mA |
Output Voltage Drop | 0 volts | 0 volts |
Off-state Leakage | 0 mA | 0 mA |
Peak Blocking Voltage | 100 VDC / 130 VAC | 100 VDC / 130 VAC |
Fuse
(Common to all Channels) |
Has four isolated channels.
User must provide own fusing. |
Has four isolated channels.
User must provide own fusing. |
Logic Side Ratings | ||
Pickup Voltage | 4 V @ 5.5 mA | 4 V @ 5.5 mA |
Dropout Voltage | 1 VDC | 1 VDC |
Control Resistance | 220 ohms | 220 ohms |
Logic Supply Voltage | 5 VDC ± 0.25 VDC | 5 VDC ± 0.25 VDC |
Logic Supply Current | 50 mA maximum | 50 mA maximum |
Module Ratings | ||
Number of Channels Per
Module |
4 | 4 |
Turn-on Time | 500 usec | 500 usec |
Turn-off Time | 500 usec | 500 usec |
Isolation
(Field Side to Logic Side) |
1,500 volts (transient) | 1,500 volts (transient) |
Mechanical Life | 200,000,000 cycles | 200,000,000 cycles |
Temperature |
0 °C to 70 °C, operating
-30 °C to 85 °C, storage |
0 °C to 70 °C, operating
-30 °C to 85 °C, storage |
Agency Approvals | CE, FM, RoHS, DFARS | CE, FM, RoHS, DFARS |
Warranty |
30 months or mechanical life,
whichever comes first |
30 months or mechanical life,
whichever comes first |
* The current of the dry contact module must not exceed 10 VA power limit under steady state or momentary in-rush
conditions. For voltages at or below 20 volts, the current limit is 0.5 amps. For voltages above 20 volts, the maximum allowable current is determined by the following equation: Current Maximum = 10 VA / Voltage. Rating curve is in the data sheet. |
Rev: 04/13