OPT-SNAP-ph-ORP

Artikel 1237 VON 1293
Zoom
OPTO 22 SNAP ph/ORP 2-channel Module
zzgl. MwSt. Gewicht: 0.3 kg RegulÀr Regulär Neu Neu
SNAP-ph-ORP SNAP-pH/ORP Differential Voltage Measurement Input Module
Opto 22 SNAP-ph-ORP Opto 22 Logo
The SNAP-pH/ORP module provides two isolated channels of high-impedence voltage input, either -1.00 to +1.00 volts
or -0.50 to +0.50 volts. The module is ideal for differential voltage measurements and is used with pH or oxidation
reduction potential (ORP) probes for monitoring bodies of water.
 
The SNAP-pH/ORP module can be used with SNAP PAC brains and R-series controllers, legacy SNAP Ethernet-based
brains, and legacy serial B3000 and B3000-B brains.
 
Input Range -1.00 V to +1.00 V for ORP probes
-0.50 V to +0.50 V for pH probes
Resolution 40 µV when configured -1.00 V to +1.00 V
20 µV when configured -0.50 V to +0.50 V
Data Freshness (Maximum) 126 ms (63 ms per channel) when configured -1.00 V to +1.00 V
251 ms (125.5 ms per channel) when configured -0.50 V to +0.50 V
Input Filtering -3 dB @ 2.4 Hz
DC Common Mode Rejection >-120 dB
AC Common Mode Rejection >-120 dB at 60 Hz
Maximum Survivable Input ±100 VDC or peak AC
Maximum Operating Common
Mode Voltage
250 VDC or peak AC
Accuracy (% full scale) 0.05% when configured -1.00 V to +1.00 V
0.05% when configured -0.50 V to +0.50 V
Gain Temperature Coefficient 30 PPM/°C
Offset Temperature Coefficient 15 PPM/°C
Power Requirements 5 VDC (±0.15) at 170 mA
Input Resistance (Differential) >10 Tera Ohms (each channel)
Ambient Temperature:
  Operating
  Storage

0 to 70 °C
-25 to 85 °C
Torque, hold-down screws 4 in-lb (0.45 N-m)
Torque, connector screws 5.26 in-lb (0.6 N-m)
Agency Approvals CE, RoHS, DFARS
Warranty Lifetime

Rev: 04/13

* zzgl. Versandkosten